What's That Burning Smell?

http://inthewilderness.net/2026/02/16/whats-that-burning-smell/

by DamonHD

7/29/2026 at 2:36:05 PM

TL/DR: author had a bad connection in their solar system. Despite having burning smell of electronics, seeing blackened wires, and having parts so hot it burned their fingers, they did nothing and kept the system active until things got so bad the inverter shut down with fault code. They got pretty lucky nothing caught on fire or melted.

Their problem was that one of the screws got loose, and their suggested fix was to re-tighten them 6 month after installation. This is a good idea. I'd also suggest using wire ferrules and not ignoring blackened wires and smells from high-current electronics.

by theamk

7/29/2026 at 6:50:14 PM

I periodically re-tighten such connections in my much-lower-powered off-grid system. 10A is the most I expect to see in any part of mine. I have had overheats from poor connections.

by DamonHD

7/29/2026 at 6:58:30 PM

> in their solar system

I hope it's not too close to my solar system!

by VMG

7/29/2026 at 4:19:14 PM

Inline fuses and breakers are a thing. Use them. Or don't. There's no electrical code in the middle of nowhere.

by 1970-01-01

7/29/2026 at 4:33:35 PM

The failure here wasn't overcurrent, which is what fuses (or breakers) mitigate. Here it was poor connection, no fuse or breaker would help. And in fact didn't since the author mentioned he had breakers on these lines.

Also, and particularly in high current circuits like these, fuses generate significant heat on their own, at the connection points.

The better bet is to look to conservative standards (like ABYC for the marine industry) and follow their rules for wire termination. In this case that would be properly crimped ring terminals over simply wrapping stranded cable around a screw. That said I am sure the NEC has something to say about domestic solar installations.

by scrumper

7/29/2026 at 4:50:15 PM

The idea is your inline fuse overheats and melts instead of the entire controller turning into fire due to the heat cooking the plastic at the rail or terminal. It's a passive device for both overcurrent and overheating. Or just step into 2026 and use mag breakers, there are lots of DC breakers that do this: https://www.amazon.com/Miniature-Circuit-Isolator-Magnetic-D...

by 1970-01-01

7/29/2026 at 6:21:20 PM

The issue wasn't heat generated by excessive current, but heat generated by excessive resistance and normal current.

Mag breakers and fuses won't help. A thermal fuse could work,provided it was thermally bonded to the bad connection. So you'll need a lot of thermal fuses - one at every potential bad connection.

by BenjiWiebe

7/29/2026 at 6:40:48 PM

Mag breaker opening under overtemp condition:

https://www.youtube.com/shorts/thUbyzO8Cek

by 1970-01-01

7/29/2026 at 6:51:09 PM

This only happens when there is an overcurrent condition. As OP, scrumper, BenjiWiebe all told you there was no overcurrent condition. The system was rated for a 100 amp, the current was under that.

The thermal overload breaker won't help here, because it only trips when the current is above breaker rating. And one would install at least a 100A breaker into a circuit rated for 100A, or it'll just trip all the time.

(You can see the detailed curve on datasheet, example page 2 here [0]. It is surprisingly slow - for 1.5X overload, it takes >10 minutes to trip).

The problem was because of bad connection on 100A line. We can talk about mistakes made here, but lack of breaker was not one of them.

[0] https://www.eaton.com/content/dam/eaton/products/electrical-...

by theamk

7/29/2026 at 7:41:24 PM

>This only happens when there is an overcurrent condition.

It happens when it gets too hot. Principle of Operation: The Bimetallic Strip Mechanism:

https://www.haipart.com/news/thermal-trip-unit-in-circuit-br...

by 1970-01-01

7/29/2026 at 8:33:06 PM

have you actually read this page?

> If the current exceeds the rated load for a prolonged period, the heat causes the bimetallic strip to bend.

> The unit trips after a delay inversely related to the magnitude of the overload; the greater the current, the faster the trip.

The heat is generated by the breaker itself, from the current. Maybe it'll trip slightly faster if the wire is very hot, but I say it's unlikely - the thermal resistance on a regular breaker is very low, and wire is not a very great heat conductor either.

And even if breaker was for some reason reacting on wire temperqture? Look at the original post. You can easily see how far the heat traveled simply by seeing where the insulation got blackened. It looks like just a few cm - nowhere close to get to the other end of the wire, which was in the breaker. The system had breaker, and it could not detect this condition.

(There are special "thermal fuses" which react on the external temperature, but they are very distinct from the regular circuit breaker, and they must be attached directly to the device emitting heat, like a motor. No one attaches those to the regular terminal strips)

by theamk

7/29/2026 at 8:52:58 PM

>The heat is generated by the breaker itself, from the current.

Why do you think this?

>You can easily see how far the heat traveled simply by seeing where the insulation got blackened. It looks like just a few cm

Why do you think this? Copper is excellent at thermal conductivity, only beaten by silver.

by 1970-01-01

7/29/2026 at 5:01:24 PM

Do you smell chicken?

by addedGone